P/N 3101185 • REV 02 • REB 28FEB13

3 / 4

PTC thermistors

Figure 1 shows the locations of the PTCs. PTC 2, 4, 6, and 8

provide output protection for speaker zones 1, 2, 3, and 4,

respectively. Each PTC is installed in a socket for easy

replacement.
The ANSZS2A and ANSZS4B are shipped with PTCs for

25 Vrms operation. These are labeled “XF 075.” For 25 Vrms

operation, leave these PTCs installed.
To configure the module for 70 Vrms operation, replace all four

PTCs with the optional PTCs provided. These are labeled

“XF 040.”

Installation instructions

Ensure that all wiring and devices installed in the system meet

the following standards:

NFPA 70 National Electrical Code

NFPA 72 National Fire Alarm and Signaling Code

NFPA 101 Life Safety Code

Applicable state and local codes

Install this equipment in a clean, dry environment. Avoid

installation where the equipment could be subjected to

vibration. Remove all electronic assemblies from the enclosure

before drilling or punching the enclosure. Where possible,

make all cable entries from the rear or sides. Before making

any modifications to the enclosure, be certain that they will not

interfere with the assemblies or batteries.
For all field wiring, use FPL, FPLR, or FPLP as required per

NFPA 70, Article 760.
All wiring shown in “Wiring diagrams” is power-limited.

Wiring diagrams

Figure 2: ANSZS4B typical wiring

(1) This resistor sets the amplifier end-of-line value only. The

ANSZS2A and ANSZS4B must use 10 kΩ EOLRs.

(2) Break the wire run at each terminal to maintain supervision. Do

not loop the wire around the speaker terminal.

ANS25 / 50 / 100

ANSZS4B

FACP

EOLR

SPKR SET

EOLR (1)

POWER

SIG

CKT

SPKR

ZONE 1
ZONE 2
ZONE 3
ZONE 4
ALL CALL

REMOTE ACTIVATION

(PULL-DOWN) INPUTS

ZONE 1

ZONE 2

ZONE 3

ZONE 4

PTT

V+

CKT NEG

SUPV OUT

SPEAKER

CONNECTION (2)

SUPERVISED

SUPERVISED

SUPERVISED

ALL ZONE SPEAKER

WIRING IS

SUPERVISED

Class B (Style Y) wiring

UNSUPERVISED

UNSUPERVISED

TB1

TB3

TB2

TB3

EOLR

10 kO EOLR

TB2

TB1

1 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8

1
2
3
4
5
6
7
8
9

10
11

11
10

9
8
7
6
5
4
3
2
1

1
2
3
4
5
6
7
8

SIG ACT

1 2 3 4 5 6 7