4 output circuits, 1 notification appliance circuits, Output circuits – Fire-Lite MS-4E Fire Alarm Control Panel User Manual

Page 22: Notification appliance circuits, Tb2 b+ b- b+ b- nac 1 nac 2

Advertising
background image

22

MS-2 & MS-4 Series Manual — P/N 51512:G2 10/18/2011

Installation

Output Circuits

2.4 Output Circuits

2.4.1 Notification Appliance Circuits

The MS-2 provides one Style Y (Class B) NAC (Notification Appliance Circuit) while the MS-4
provides two Style Y (Class B) NACs. Each circuit is capable of providing a maximum of 2.5
amps of current. Total current drawn from these as well as other DC power outputs cannot exceed
3.0 amps for the MS-2 or 6.0 amps for the MS-4 with the optional second transformer installed
(refer to battery calculations section). Each circuit is supervised and power-limited. Refer to the
Fire•Lite Device Compatibility Document for a listing of compatible notification appliances.

The MS-4 NACs can be converted to Style Z (Class A) by installing the optional Class A Converter
module. Refer to “CAC-4 Class A Converter Module (MS-4 only)” on page 25.

TB2

B+ B- B+ B-
NAC 1 NAC 2

Figure 2.6 NAC Connections

Class B Notification Appliance Circuits (supervised and power-limited)

4.7 K

, ½ watt resistor P/N:71252

Dummy load any unused
circuits (P/N: 71245)

Polarized Bell

Polarized Strobe

Polarized Horn

Polarized Horn

Polarized Horn-Strobe

Polarized Bell

Notification Appliance Circuit
polarity shown in alarm condition

m

s-4n

a

c.

w

m