Fire-Lite MS-4E Fire Alarm Control Panel User Manual

Page 8

Advertising
background image

8

MS-2 & MS-4 Series Manual — P/N 51512:G2 10/18/2011

MS-2 Two Zone Main Circuit Board

J7 Transformer
Connector

120 VAC, 2.3A or
220/240 VAC, 1.15A
Earth
Neutral
Hot
(supervised,
nonpower-limited)

J8 Battery Connector
(supervised, nonpower-limited)
18 Amp Hour max.

Charger Fault LED
Battery Fault LED
Earth Fault LED

SW1, SW2 and SW3
Programming DIP Switches
Note: Factory-installed cover
removed for illustration
purposes only!

24 VDC Special Application

Resettable Power

500 mA max. (nonsupervised,

power-limited)

- 24 VDC

+ 24 VDC

NAC (4.7KW, ½ watt ELR)

2.5A max.

(supervised, power-limited)

B-

B+

IDC (4.7 K

, ½ watt ELR)

(supervised, power-limited)

Zone 2 B-

Zone 2 B+

Zone 1 B-

Zone 1 B+

Trouble Relay (fail-safe)
2 amps @ 30 V

DC

(nonsupervised)
Common
Trouble (Normally Open)
Normal (Normally Closed)

Alarm Relay
2 amps @ 30 V

DC

(nonsupervised)
Common
Normally Closed
Normally Open

ms2

b

ord

.wmf

JP3 - Cut to disable
Ground Fault
detection (only with
approval of AHJ)

J3 and J5

4XTMF Option

Module

Connectors

Module Placement Supervision (if installed)
JP1 - cut to supervise module on J3 & J5