MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

71

Master Programming Level

Programming

Pre-signal Delay

The factory default setting for Pre-signal delay is 000 for no delay. To select a Pre-signal delay of
001 to 180 seconds for all devices programmed for Pre-signal, press 2 while viewing Timer Screen
#1. The following screen will be displayed:

A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting
of three digits, such as 009 for nine seconds. Upon entering the third digit, the time delay will be
stored in the control panel memory and the display will return to the Delay Screen which will indi-
cate the new delay time.

Note that the FACP can have both PAS and Pre-signal timers programmed with values but a zone
can only use either the PAS or Pre-signal feature, but not both.

Waterflow Delay

A delay can be added prior to declaring a waterflow type of alarm. Be careful to include any built-
in delays of the waterflow device. The factory default setting for Waterflow delay is 000 for no
delay. To select a Waterflow delay of 01 to 90 seconds for all devices programmed for Waterflow
delay, press 3 while viewing Timer Screen #1. The following screen will be displayed:

A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting
of two digits, such as 25 for twenty-five seconds. Upon entering the second digit, the time delay
will be stored in the control panel memory and the display will return to the Delay Screen which
will indicate the new delay time.

AC Loss Delay

The reporting of a loss of AC power to a central station can be delayed by programming the length
of the desired delay. Press 1 while viewing Timer Screen #2 to display the following:

A flashing cursor will appear in the lower left corner of the display. The factory default setting is
02 hours. Type the two digit AC loss reporting delay in hours (00 to 24 hour delay). When the sec-
ond digit is entered, the display will return to AC Loss Delay Screen #1.

PRESIGNAL DELAY

RANGE 000-180 SECONDS

Pre-signal Delay Screen

TIMER

1=PAS DELAY 120

2=PRE SIGNAL 120

3=WATERFLW DELAY 0

Timer Screen #1

WATERFLOW DELAY

RANGE 00-90 SECONDS

Waterflow Delay Screen

TIMER

1=AC LOSS DELAY 2

Timer Screen #2

AC LOSS DELAY

RANGE 00-24 HOURS

AC Loss Delay Screen #1

NOTE: Upon the loss of AC power at the control panel, relays programmed for AC Loss will
transfer immediately, regardless of the AC Loss Delay setting. If no troubles other than AC Loss
exist in the panel, the System Trouble relay will delay activation for the duration of the AC Loss
Delay
setting.