Ann-rly options screen – Fire-Lite MS-10UD Series FACP User Manual

Page 78

Advertising
background image

78

MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

Programming

Master Programming Level

The Silence Button Enable (SIL BTN ENABLE) option allows the programmer to select whether the
Silence button on any installed ANN-80 annunciator will function normally or always be ignored.
Pressing 1 while viewing the ANN-80 Options Screen #2 causes the display to toggle between Sil
Btn Enable Yes
(Silence button functions normally) and Sil Btn Enable No (Silence button never
functions).

The Reset Button Enable (RST BTN ENABLE) option allows the programmer to select whether the
Reset button on any installed ANN-80 annunciator will function normally or always be ignored.
Pressing 2 while viewing the ANN-80 Options Screen #2 causes the display to toggle between Rst
Btn Enable Yes
(Reset button functions normally) and Rst Btn Enable No (Reset button never func-
tions).

The Drill Button Enable (DRL BTN ENABLE) option allows the programmer to select whether the
Drill button on any installed ANN-80 annunciator will function normally or always be ignored.
Pressing 3 while viewing the ANN-80 Options Screen #2 causes the display to toggle between Drl
Btn Enable Yes
(Drill button functions normally) and Drl Btn Enable No (Drill button never func-
tions).

ANN-RLY Options Screen

Pressing 3 for ANN-RLY Options while viewing ANN-BUS Screen #2 will cause the following
screen to be displayed:

The ANN-RLY module provides ten Form-C relays which can be programmed for various func-
tions. The initial screen displays Relays 1 through 3. Pressing the down arrow key will display the
remaining relays for this module.

To program any of the ANN-RLY relays, while viewing the appropriate ANN-RLY Option screen,
press the number key corresponding to the relay to be programmed. Following is a list of the avail-
able programming options for each relay:

General Alarm

General Trouble

General Supervisory

AC Loss

Waterflow Delay

Input Zone 1

Input Zone 2

Input Zone 3

Input Zone 4

Input Zone 5

Input Zone 6

Input Zone 7

Input Zone 8

Input Zone 9

Input Zone 10

Silenceable Alarm

Not Assigned

PROGRAMMING

1=ANN-S/PG OPTIONS

2=ANN-80 OPTIONS

3=ANN-RLY OPTIONS

ANN-BUS Screen #2

ANN-RLY OPTIONS

1=RELAY 1 IN ZONE 1

2=RELAY 2 IN ZONE 2

3=RELAY 3 IN ZONE 3

ANN-RLY Options Screen