Panel Mounting

Notes:

1.

This arrangement allows use of the UDACT-F simultaneously with the RTM-8F module

2.

Ferrite cores are recommended for all applications

3.

Recommended wire is 12 AWG to 18 AWG (0.75 to 3.25 mm

2

) twisted wire

4.

Shielded wire is not required (unless mandated by local AHJ)
If shield wire is used, connect only one end of the shield:

✓ shield may be connected to cabinet (earth ground) at fire alarm panel, or
✓ shield may be connected to TB1 Terminal 5 (shield) at UDACT-F as shown in Figure 2-3. Note that the

shield end that is not connected should be insulated to prevent accidental grounding. Do not connect
both ends of the shield under any circumstance, since a ground fault may result.

5.

Conduit is recommended for external wire runs. Consult local building codes

6.

Connect Ground Strap (supplied with ABS-8RF enclosure) from Earth Ground terminal on the UDACT-F to a
solid building earth ground. Conduit alone will not provide a reliable earth ground.

7.

UDACT-F may be located up to 6,000 feet (1,800 m) away from the host control panel

8.

Refer to “Specifications” on page 10, for power requirements

FIGURE 2-3:

External UDACT-F Mounting in ABS-8RF - MS-9200

MS-9200

UDACT-F in ABS-8RF
(shown with cover removed)

Install 120 ohm EOL resistor
(P/N 71244) on TB1 Terminals
3 & 4, if last or only device on
EIA-485 line.

MS-9200 cabinet

Ferrite Cores

P/N FBD-1

24 VDC

Nonresettable

Power

To Phone

Lines

(Supervised)

Solid Earth

Ground

Connection

DO NOT USE

THESE TERMINALS

Supervised and power-limited EIA-485 and power connections