39

Programming Options

Ademco Contact ID Format

If 'E' is entered for address 42, the following data is automatically programmed for the Secondary phone number
event codes. Enter '000' for the data setting to disable the report.

Notes:

1.

Zero entries prevent the transmission of the report to the Central Station

2.

Refer to Contact ID program locations 64 - 68

3.

The identification of the zone/sensor number is automatically transmitted by the UDACT-F and is added to the
main event code. Refer to Table A-3, “Ademco Contact ID Reporting Structure,” on page 49, for additional
information

4.

Factory default for this report is 110 (110 is transmitted for modules, however, 111 will automatically be trans-
mitted for smoke detectors). Use Type Mode (refer to “Type Mode” on page 44) to change this report per zone
or point

TABLE 3-7:

Ademco Contact ID Secondary Number

Address

Description

Setting

1

Sensor Number

139 - 141

Secondary # General Alarm Code

110

000

2

142 - 144

Secondary # Zone/Point Alarm Code

110

4

Note

3

145 - 147

Secondary # General Supervisory Code

200

000

2

148 - 150

Secondary # Zone/Point Supervisory Code

200

Note

3

151 - 153

Secondary # General Fault Code

300

154 - 156

Secondary # AC Fault Code

301

157 - 159

Secondary # Zone/Point Fault Code

380

Note

3

160 - 162

Secondary # Low Battery Fault Code

302

163 - 165

Secondary # Telco Primary Line Fault Code

351

166 - 168

Secondary # Telco Secondary Line Fault Code

352

169 - 171

Secondary # NAC Fault Code

321

172 - 174

Secondary # Communication Trouble Primary # Code

354

175 - 177

Secondary # Communication Trouble Secondary # Code

354

178 - 180

Secondary # 485 Communication Trouble Code

300

181 - 183

Secondary # System Off Normal Code

308

184 - 186

Secondary # UDACT-D Off Normal Code

350

187 - 189

Secondary # System 24 Hour Test

602

190 - 192

Secondary # System 24 Hour Test with Active Event

608

193 - 195

Secondary # Manual Test Message

601