3
2-2. Constant Voltage Operation
(1) Output Voltage ranges from 0 to rating voltage with continuous adjustment.
(2) Voltage regulation
line regulation≦5mV.
load regulation≦5mV.
(3) Recovery time≦500μs(50% Load change, minimum load 0.5A).
(4) Ripple & Noise≦5mVrms, 100mVp-p (tested by 20MHz oscilloscope.)
(5) Temperature coefficient≦100ppm/℃.
2-3. Constant Current Operation
(1) Output current ranges from 0 to rating current with continuous adjustment.
(2) Current regulation
line regulation≦3mA.
load regulation≦3mA.
SPS-606
SPS-3610
SPS-2415
SPS-1820
SPS-1230
(3) Ripple & Noise
≦3mArms
≦5mArms
≦10mArms
≦10mArms
≦30mArms
2-4. Indicator Meter
1)Voltage:
Display
: 3 1/2 Digits 0.39” Green LED display.
Accuracy
: ±(0.5% of rdg + 2 digits).
2)Current:
Display
: 3 1/2 Digits 0.39” Red LED display.
Accuracy
: ±(0.5% of rdg + 2 digits).
2-5. Over Voltage Protection
(1) Over Voltage Protection ranges from 5% rating to rating +5.5%.
(2) OVP Accuracy ±(Vset 1%+0.6V)
2-6. Insulation
Between Chassis and Output Terminal
: ≧
20MΩ (DC500V).
Between Chassis and AC Cord
: ≧
30MΩ (DC500V).