Technical specifications – HT instruments PQA820 User Manual

Page 21

Advertising
background image

PQA820

EN – 20

11. TECHNICAL

SPECIFICATIONS

11.1. TECHNICAL CHARACTERISTICS

Accuracy indicated as

[%rdg +(num. dgt * resolution)] referred to 23°C±5°C, < 75%RH

DC Voltage [Phase (+) – Neutral (-)]

Range [V]

Resolution [V]

Accuracy

10.0

265.0

0.1

(0.7rdg + 0.4V)

Voltage values <10.0V are zeroed

AC TRMS Voltage (Phase-Neutral, Phase-PE)

Range [V]

Frequency [Hz]

Resolution [V]

Accuracy

10.0

265.0

42.5

69.0Hz

0.1

(0.5rdg + 0.2V)

Maximum crest factor = 1.5, Voltage values <10.0V are zeroed

AC TRMS Voltage (Phase- Phase)

Range [V]

Frequency [Hz]

Resolution [V]

Accuracy

50.0

 460

42.5

 69.0Hz

0.1

(1.0rdg + 0.2V)

Maximum crest factor = 1.5, Voltage values <10.0V are zeroed

Voltage anomalies (Phase-Neutral, Phase-PE)

Range [V]

Resolution [V]

Resolution [ms]

Accuracy [V]

Accuracy [ms]

15.0

265.0

0.2 10ms

(1.0

rdg + 2dgt)

½ cycle

DC Current – STD transducers clamps

Range [mV]

Resolution [mV]

Accuracy

Overload protection

5.0

219.9

1

(0.7rdg + 1mV)

10V

220.0

999.9

0.7rdg

Current values correspondent to a voltage < 5mV are zeroed

AC TRMS Current – STD transducers clamps

Range [mV]

Frequency [Hz]

Resolution [mV]

Accuracy

5.0

219.9

42.5

69.0Hz

1

(0.5rdg + 0.6mV)

220.0

999.9

(0.5rdg)

Current values correspondent to a voltage < 5mV are zeroed

AC TRMS Current – Flex transducers clamps (100A AC Range – 85

V/A)

Range [A]

Frequency [Hz]

Resolution [A]

Accuracy

Overload

protection

0.085

 8.50

42.5

 69.0Hz

8.5

V

(0.5rdg+0.007mV)

10V

Maximum crest factor = 1.5, Current values <1A are zeroed

AC TRMS Current – Flex transducers clamps (1000A AC Range – 85

V/A)

Range [A]

Resolution [A]

Accuracy

0.425

 85.0

42.5

 69.0Hz

85

V

(0.5rdg+0.15mV)

10V

Maximum crest factor = 1.5; Current values <5A are zeroed


Frequency

Range [Hz]

Resolution [Hz]

Accuracy

42.5

 69.0

0.1

(0.2rdg + 0.1Hz)



DC Power – (Vmeas > 200V)

Clamp FS [A]

Range [W]

Resolution [W]

Accuracy

1< FS

 10

0.000k

 9.999k

0.001k

(1.0rdg + 5W)

10.00k

 99.99k

0.01k

(1.0rdg + 50W)

10< FS

 200

0.00k

 99.99k

0.01k

(1.0rdg + 50W)

100.0k

 999.9k

0.1k

(1.0 rdg + 500W)

200< FS

 1000

0.0k

 999.9k

0.1k

(1.0rdg + 0.5kW)

1000k

 9999k

1k

(1.0 rdg + 5kW)

Vmeas = Voltage in which the power is measured