2 front panel access, 3 keying, 4 output voltage control – KEPCO HSF 600W Series (suffix A and AM) Operator Manuals User Manual

Page 10: 1 front panel voltage control, R. 3.4.1

Advertising
background image

8

HSF(A) 600W 101013

3.2

FRONT PANEL ACCESS.

The front panel provides a power ON/OFF switch controlling input power and a "VDC ON" indica-

tor which lights green when the unit is operating. If the unit is connected in a parallel configuration,

the indicator lights red if the unit shuts off automatically, or the POWER switch is set to OFF.

CAUTION: DO NOT repeatedly toggle the power ON/OFF switch as this may cause unit to

fault.

NOTE: The ON/OFF switch must be set to OFF before removing unit from rack adapter.

If remote on-off is not enabled (see PAR. 3.5), the OUTPUT RESET button restores output power

in the event that overcurrent or overvoltage protection has tripped, or thermal overload or fan mal-

function has occurred.

If remote voltage control (see PAR. 3.4.2) is not enabled, the front panel Vadj trimmer (see PAR.

3.4.1) provides adjustment of the output voltage within the limits specified in Table 2; test points

are available at the front panel for monitoring the DC output.

Figure 5 shows the location of all operating controls, indicators and test points followed by an

explanation of each.

3.3

KEYING

Keying of the HSF (A, AM) 600W is established at the factory. The output voltage determines

which key pins are installed (see Figure 3, Detail A). When the proper holes in the rack adapter

are blocked by keying screws installed by the user, only a power supply of the correct voltage can

be inserted in the rack adapter slot. Refer to the RA 19-4C Manual for rack adapter keying instruc-

tions.

3.4

OUTPUT VOLTAGE CONTROL

Output Voltage can be controlled from either the front panel (PAR. 3.4.1) or externally using a

trimpot or voltage source (PAR. 3.4.2).

3.4.1 FRONT PANEL VOLTAGE CONTROL

Output voltage can be manually adjusted with the voltage adjustment control, Vadj (see Figure 5

for location). Configuration options are as follows:

Output from maximum to minimum specified in Table 2 (Figure 6A (factory default)).

SW1: pos 1 to ON, pos 2 to ON;

SW2: pos 1 to OFF, pos 2 to OFF, pos 7 to OFF

Output from maximum to 0V (requires multiple turns of Vadj for full range)

SW1: pos 1 to OFF, pos 2 to OFF

SW2: pos 1 to ON, pos 2 to ON, pos 7 to ON

To adjust voltage, first place the unit under an operating load. Then monitor the (+) and (–) test

points on the front panel with a precision voltmeter and turn the voltage control to the desired

operating value.

The minimum output voltage required to ensure proper operation of the alarm relay, meter (on AM
models) and LED indicator is listed in Table 5.