Electrical connections – KROHNE IFC 100 Converter Quickstart EN User Manual
Page 21

ELECTRICAL CONNECTIONS
3
21
IFC 100
www.krohne.com
07/2010 - 4000124104 - QS IFC 100 R04 en
Connecting the signal and field current cables
Connect the electrical conductors as follows:
1 Push the lever downwards with a screwdriver in good condition (blade: 3.5 mm wide and
0.5 mm thick).
2 Insert the electrical conductor into the plug.
3 The conductor will be clamped as soon as the lever is released.
Figure 3-8: Function of the electrical connection terminal
Figure 3-9: Connecting the signal and field current cables
1 Cable entry for field current cable
2 Cable entry for signal cable
3 Connecting the field current cable shield
4 Electrical conductor (7)
5 Electrical conductor (8)
6 Stranded drain wire (1) of the inner shield (10) of the signal cable
7 Electrical conductor (2)
8 Electrical conductor (3)
9 Stranded drain wire (S) of the outer shield (60)