Modbus protocol – KROHNE IFC 050 Converter Modbus EN User Manual
Page 11

MODBUS PROTOCOL
6
11
IFC 050
www.krohne.com
09/2012 - 4002202601 - AD Modbus IFC 050 R01 en
6.6.2 Counter controls
6.6.3 Start calibration functions
Modbus protocol
address
Description
Settings
Converter Fct. No.
3000
Start / Stop
Counter 1
Write
1
start counter
C3.1.5 / C3.1.6
Write
0
stop counter
Read
1
counter is running
Read
0
counter is stopped
3001
Start / Stop
Counter 2
Write
1
start counter
C3.2.5 / C3.2.6
Write
0
stop counter
Read
1
counter is running
Read
0
counter is stopped
3003
Reset Counter 1
Write
1
reset counter
C3.1.3
Write
0
-
Read
0
-
3004
Reset Counter 2
Write
1
reset counter
C3.2.3
Write
0
-
Read
0
-
Modbus protocol
address
Description
Settings
Converter Fct. No.
2000
Zero Calibration
Write
1
start function
C1.1.1
Write
0
-
Read
1
calibration running
Read
0
calibration finished
2001
Electrode Factor
Calibration
Write
1
start function
C1.1.8
Write
0
-
Read
1
calibration running
Read
0
calibration finished