Local configuration – KROHNE IFC 100 Converter Modbus EN User Manual
Page 6

4
LOCAL CONFIGURATION
6
IFC 100
www.krohne.com
08/2014 - 4001410101 - AD Modbus IFC 100 R01 en
Local configuration
Converter Fct.
No.
Display
Description and settings
C5.8.1
Slave Address
Selects the Modbus address of the device.
Range: 1..247 (default = 1)
C5.8.2
Baud Rate
Selects the baud rate of the device.
Options:
1200 / 2400 / 3600 / 4800 / 9600 / 19200 (default) / 38400 / 57600 / 115200
C5.8.3
Parity
Selects the parity.
Options:
Even (default) / Odd / No
C5.8.4
Data Format
Selects the data format.
Options:
Big Endian (default) / Little Endian
C5.8.5
Transmission Delay
Selects the delay between receiving the last byte of a request and
sending the first byte of the response.
Range: 0..40ms (default = 0ms)
C5.8.6
Stop Bits
Selects the number of stop bits.
Options:
1 (default) / 2
C5.8.7
Information
Displays information about the device.
.book Page 6 Monday, July 28, 2014 11:32 AM