Technical data
2.1 Foundation Fieldbus data
Description
Type
Electromagnetic flowmeter
Physical layer
Foundation Fieldbus protocol that agrees with IEC 61158-2 and FISCO model;
galvanically isolated
Communication standard
H1
ITK version
5.2
Data blocks
Function blocks
1 x Enhanced Resource Block (RB)
1 x Customer Transducer Block (TB)
3 x Analog Input Block (AI)
2 x Integrator Block (IT)
1 x Proportional Integral Derivate Block (PID)
Execution time
Analog Input Block: 10 ms
Integrator Block: 15 ms
Proportional Integral Derivate Block: 25 ms
Electrical connections
Device power supply
Not intrinsically safe: 9...32 VDC
Intrinsically safe: 9...24 VDC
Basic current
10.5 mA
Maximum error current
16.5 mA (= basic current + error current = 10.5 mA + 6 mA)
Start current after 10 ms
14 mA
Polarity sensitivity
No
Minimum cycle time
250 ms