Temperature limits, 1 compact versions – KROHNE OPTIFLUX 2000-4000-5000-6000-7300-IFC 300 Ex EN User Manual

Page 18

Advertising
background image

2

TEMPERATURE LIMITS

18

OPTIFLUX

www.krohne.com

07/2010 - 7309482600 - AD EX IFC 300 R06 en

The temperature limits apply under the following conditions:

• The instrument is installed and operated in accordance with the installation directions given

in the installation and operating instructions.

• The instrument is not heated up by any additional heat radiation (direct solar radiation, heat

from adjacent plant parts) so causing it to operate above the permissible ambient
temperature range.

• Insulation is not hindering free ventilation of the signal converter housing.

2.1 OPTIFLUX 2000 / 4000

2.1.1 Compact versions

• The OPTIFLUX 2300 C / 4300 C is suitable for an ambient temperature range of

-40…+60°C.

• For dust hazardous areas, the maximum surface temperature is equal to the process

temperature with a minimum of 85°C.

• The minimum process temperature for all DN sizes is -40°C.
• The maximum process temperature is determined by the temperature class T6/T5...T3 of the

gas hazardous area of concern, the maximum ambient temperature (T

a

), and the nominal

diameter. The temperature range is often limited further by the liner type used (refer to the
Quick Start).

DN2.5...15 ("me")

DN10...20 ("me")

Temperature class

Max. process temperature Tp [°C]

T

a

≤ 40°C

40 < T

a

≤ 50°C

50 < T

a

≤ 60°C

T6

70

70

60

T5

85

85

60

T4

120

120

60

T3

150

140

60

Temperature class

Max. process temperature Tp [°C]

T

a

≤ 40°C

40 < T

a

≤ 50°C

50 < T

a

≤ 60°C

T6

70

60

-

T5

95

85

60

T4

130

130

60

T3

150

150

1

60

1 140°C for versions with stainless steel converter housing