KROHNE VFM 5090 EN User Manual

Page 23

Advertising
background image

5.7.2 OUTPUT TYPE

1. RS-232

OUTPUT


The RS-232 output option provides a means for communication of measured values to remote system. At present,
this communication is in one direction only [from VFM 5090(I) to remote system]. Measured values as well as
Error Messages which appear on the instrument display in the normal measurement mode are output on RS-232
line. When the RS-232 output option is present, the usual frequency output function cannot be used.

1.1 RS-232

OUTPUT

The RS-232 output is galvanically isolated from all inputs and output circuits but not from current output.

Therefore, only one grounded receiver may be connected to either RS-232 output or current output. Note that
connecting RS-232 to IBM PC/compatibles will ground the RS-232 output.

·

·

·

Operating data for RS-232 output is not programmable as in case of current or frequency output. VFM

5090(I) always uses the following operating data : 1 Start bit, 8 Data bits, No Parity, 1 Stop bit at a baud rate of
1200 bits/sec.

Connection diagram for RS-232 output is given below. Please note that the RS-232 output uses the same

terminals as used by the Frequency output. Consequently, when the RS-232 option is present, frequency output
function can not be used.


5
+

6
-

4
RXD

4.1
TXD

4.2
GND

1.2 CHARACTER

FORMAT

Measured values or Error messages which appear on instrument display in normal measuring mode are coded as
series of 8-bit characters or “bytes”. These are transmitted serially, using a conventional UART (Universal
Asynchronous Receiver/Transmitter) function to serialize each byte. As in RS-232 or other asynchronous
communication, a start bit and stop bit are added to each byte. This allow the receiving UART to identify the start
of each character.

A single 8-bit byte is sent as the following sequence of 1’s and 0’s.

0 DO D1 D2 D3 D4 D5 D6 D7 1

Start bit <---------------------8 Data Bits -----------------------> Stop bit

Baud Rate is 1200 bits/sec. All characters are encoded in ASCII character format.

1.3 DATA

FORMAT

Format for transmitting Measured values or Error messages is as follows :

Measured

Value

<SP>
<SP>

unit

<CR> <LF>

#nn Err#

<SP>
<SP>

error
mesg.

<CR> <LF>

20

Advertising