Installation, 4 general requirements – KROHNE BM 26 BASIC_ADVANCED Quickstart EN User Manual
Page 7

INSTALLATION
2
7
BM 26 BASIC/ADVANCED
www.krohne.com
10/2012 - 4000346904 - QS BM 26 Basic-Adv R04 en
2.4 General requirements
2.4.1 How to attach the bypass level indicator to the tank
Obey the instructions that follow:
• Select bolts and gaskets (not supplied) that agree with the pressure rating of the process
connection and the operating pressure.
• Install the bypass level indicator vertically on the tank.
• Make sure that there is no contamination (dirt etc.) or unwanted objects in the measuring
chamber.
• Make sure that mechanical loadings do not cause damage to the process connections. If
necessary, put supports on the device.
• Install shut-off valves so that the device can be cleaned separately from the tank. Drain the
device only when it is isolated from the tank.
Figure 2-5: How to attach the bypass level indicator to the tank
1 Optional isolation valve
2 Optional vent
3 Optional drain with isolation valve