KROHNE OPTISWITCH 3100C NAMUR EN User Manual

Page 32

Advertising
background image

Potentiometer for switching point adap-

tation

0.02 … 0.1 g/cm³ (0.0007 … 0.036 lbs/in³)

Simulation key

simulation of a line break between sensor and

processing unit

Voltage supply
Supply voltage (standard characteris-

tics)

for connection to amplifier according to NA-

MUR IEC 60947-5-6, approx. 8.2 V

Open-circuit voltage

U

0

approx. 8.2 V

Shortcircuit current

I

U

approx. 8.2 mA

Electrical protective measures
Protection

IP 66/IP 67

Overvoltage category

III

Protection class

II

Approvals

2)

ATEX II 1G, 1/2G, 2G EEx ia IIC T6 + ATEX II 1/2 D IP66 T
ATEX II 1/2G, 2G EExd d IIC T6
ATEX II 1/2 D IP66 T

3)

2)

Deviating data in Ex applications: see separate safety instructions.

3)

See temperature statements in the safety instructions manual