4 Mounting

4.1 General instructions

In general, OPTISWITCH 3200 C can be mounted in any

position. The instrument must be mounted in such a way that

the vibrating element is at the height of the requested switching

point.

Use the recommended cables (see chapter "Connecting to

power supply") and tighten the cable gland.
You can give your OPTISWITCH 3200 C additional protection

against moisture penetration by leading the connection cable

downward in front of the cable entry. Rain and condensation

water can thus drain off. This applies mainly to mounting

outdoors, in areas where moisture is expected (e.g. by

cleaning processes) or on cooled or heated vessels.

Fig. 2: Measures against moisture penetration

Do not hold OPTISWITCH 3200 C on the vibrating element.

Especially with flange and tube versions, the sensor can be

damaged by the weight of the instrument.
Remove the protective cover just before mounting.

The process fitting must be sealed if there is gauge or low

pressure in the vessel. Before use, check if the seal material is

resistant against the measured product and the process

temperature.
The max. permissible pressure is stated in the "Technical

data" in the "Supplement" or on the type label of the sensor.

Switching point

Moisture

Transport

Pressure/Vacuum

10

OPTISWITCH 3200 C - with two-wire output

Mounting