Wrong mode selected
à
Set the mode switch on OPTISWITCH 3300 C to
"max". Set the correct mode on the signal conditioning
instrument (A: overfill protection; B: dry run protection).
?
Signal lamp flashes red
l
Electronics has detected a failure
à
Exchange instrument or return instrument for repair
7.3 Exchange the electronics
In general, all oscillators of series WE60 can be interchanged.
If you want to use an oscillator with a different signal output,
you can download the corresponding operating instructions
manual from our homepage under Downloads.
With EEx d instruments, the housing cover must only be
opened if there is no explosive atmosphere.
Proceed as follows:
1 Switch off power supply
2 Unscrew the housing cover
3 Lift the opening levers of the terminals with a screwdriver
4 Pull the connection cables out of the terminals
5 Loosen the two screws with a screw driver (Torx size T10
or slot 4)