KROHNE OPTISWITCH 5100C 2wire EN User Manual
Page 30
Electromechanical data
Cable entry/plug
2)
- Single chamber housing
l
1x cable entry M20x1.5 (cable-ø 5 … 9 mm),
1x blind stopper M20x1.5
or:
l
1x closing cap ½ NPT, 1x blind plug ½ NPT
or:
l
1x plug (depending on the version), 1x blind
plug M20x1.5
Screw terminals
for wire cross-section up to 1.5 mm²
(0.0023 in²)
Adjustment elements
Sensitivity switch
- 0.5
0.5 … 2.5 g/cm³ (0.018 … 0.9 oz/in³)
- 0.7
0.7 … 2.5 g/cm³ (0.025 … 0.9 oz/in³)
Voltage supply
Supply voltage
11 … 36 V DC (via the signal conditioning
instrument)
Electrical protective measures
Protection
IP 66/IP 67
Overvoltage category
III
Protection class
II
Approvals
3)
ATEX II 1G, 1/2G, 2G EEx ia IIC T6
ATEX II 1/2G, 2G EExd d IIC T6
4)
Overfill protection acc. to WHG
Ship approvals
2)
Depending on the version M12x1, according to DIN 43650, Harting, Am-
phenol-Tuchel, 7/8" FF.
3)
Deviating data in Ex applications: see separate safety instructions.
4)
Only with Aluminium housing.
Supplement
30
OPTISWITCH 5100 C, 5150 C - with two-wire output
30430
-EN
-060831