When used in adhesive and viscous products, the tuning fork

should protrude into the vessel to avoid buildup. For that

reason, sockets for flanges and mounting bosses should be

avoided when mounting horizontally.

If OPTISWITCH 5100 C, 5150 C is mounted in the filling

stream, unwanted switching signals may be generated. Mount

OPTISWITCH 5100 C, 5150 C at a location in the vessel

where no disturbing influence from e.g. filling openings,

agitators etc. can occur.

To minimise flow resistance caused by the tuning fork,

OPTISWITCH 5100 C, 5150 C should be mounted in such a

way that the surfaces of the blades are parallel to the product

movement.

Instruments with enamel coating should be treated very

carefully and shocks should be avoided. Unpack OPTI-

SWITCH 5100 C, 5150 C directly before installation. Insert

OPTISWITCH 5100 C, 5150 C carefully into the vessel

opening and avoid touching any sharp vessel parts.