The chronological sequence of pfd – KROHNE OPTISWITCH 3x00C 2wire SIL EN User Manual
Page 23

Overflow protection
(max. operation)
Dry run protection
(min. operation)
PFD
avg
T
Proof
=
1 year
T
Proof
=
5 years
T
Proof
=
10 years
<
0.016 x 10
-2
<
0.078 x 10
-2
<
0.156 x 10
-2
<
0.016 x 10
-2
<
0.081 x 10
-2
<
0.162 x 10
-2
PFH
<
0.036 x 10
-6
/h
<
0.037 x 10
-6
/h
The chronological sequence of PFD
avg
is nearly linear to the
operating time over a period up to 10 years. The above values
apply only to the T
Proof
interval after which a recurring function
test must be carried out.
1
5
10
T
Proof
PFD
avg
1
2
3
4
Fig. 1: Chronological sequence of PFD
avg
(figures see above charts)
1
PFD
avg
= 0
2
PFD
avg
after 1 year
3
PFD
avg
after 5 years
4
PFD
avg
after 10 years
Multiple channel architecture
If the measuring system is used in a multiple channel
architecture, the safety-relevant characteristics of the selected
structure of the meas. chain must be calculated specifically for
the selected application according to the above failure rates.
A suitable Common Cause Factor must be taken into account.
Time-dependent proc-
ess of PFD
avg
Specific characteristics
OPTISWITCH series 3000 • - two-wire
23
Functional safety
32745
-
EN
-
080414