The chronological sequence of pfd, Single channel architecture (1oo1d) – KROHNE OPTISWITCH 3x00C NAMUR SIL EN User Manual
Page 10

Overflow protection
(max. operation)
Dry run protection
(min. operation)
λ
sd
12 FIT
36 FIT
λ
su
160 FIT
155 FIT
λ
dd
390 FIT
366 FIT
λ
du
47 FIT
52 FIT
DC
S
7 %
19 %
DC
D
89 %
88 %
MTBF = MTTF + MTTR
1.56 x 10
6
h
1.56 x 10
6
h
Diagnosis test period
<
100 sek.
Single channel architecture (1oo1D)
SIL
SIL
2
HFT
0
Sensor type
Type B
Overflow protection
(max. operation)
Dry run protection
(min. operation)
SFF
92 %
91 %
PFD
avg
T
Proof
=
1 year
T
Proof
=
5 years
T
Proof
=
10 years
<
0.021 x 10
-2
<
0.104 x 10
-2
<
0.207 x 10
-2
<
0.023 x 10
-2
<
0.114 x 10
-2
<
0.228 x 10
-2
PFH
<
0.047 x 10
-6
/h
<
0.052 x 10
-6
/h
The chronological sequence of PFD
avg
is nearly linear to the
operating time over a period up to 10 years. The above values
apply only to the T
Proof
interval after which a recurring function
test must be carried out.
Failure rates
Fault reaction time
Specific characteristics
Time-dependent proc-
ess of PFD
avg
10
OPTISWITCH series 3000 • - NAMUR
Functional safety
32742
-EN
-080414