KROHNE OPTISWITCH 5xx0C Contactless SIL EN User Manual
Page 9

Sensor type
Type A
Overflow protection
(max./A-operation)
Dry run protection
(min./B-operation)
SFF
88 %
88 %
PFD
avg
T
Proof
=
1 year
T
Proof
=
5 years
T
Proof
=
10 years
<
0.015 x 10
-2
<
0.072 x 10
-2
<
0.145 x 10
-2
<
0.015 x 10
-2
<
0.073 x 10
-2
<
0.147 x 10
-2
PFH
<
0.033 x 10
-6
/h
<
0.034 x 10
-6
/h
The chronological sequence of PFD
avg
is nearly linear to the operating
time over a period up to 10 years. The above values apply only to the
T
Proof
interval after which a recurring function test must be carried out.
1
5
10
T
Proof
PFD
avg
1
2
3
4
Fig. 1: Chronological sequence of PFD
avg
(figures see above charts)
1
PFD
avg
= 0
2
PFD
avg
after 1 year
3
PFD
avg
after 5 years
4
PFD
avg
after 10 years
Multiple channel architecture
If the measuring system is used in a multiple channel architecture, the
safety-relevant characteristics of the selected structure of the meas.
chain must be calculated specifically for the selected application
according to the above failure rates.
A suitable Common Cause Factor must be taken into account.
Time-dependent proc-
ess of PFD
avg
Specific characteristics
OPTISWITCH series 5000 • - contactless electronic switch
9
1 Functional safety
32746
-
EN
-
100128