Installation – KROHNE PTITEMP TT 20 C EN User Manual
Page 12

3
INSTALLATION
12
OPTITEMP TT 20
www.krohne.com
10/2011 - 4000753102 - MA OPTITEMP TT 20 R02 en
WARNING!
The transmitter has been developed for an operating temperature of -40...+85°C/ -40°F...+185°F.
To avoid destruction or damage of the device, always assure that the operating temperature or
ambient temperature does not exceed the permissible range. The thermowell also transfer the
process temperature to the transmitter housing. If the process temperature is close to or
exceeds the maximum temperature of the transmitter, then the temperature in the transmitter
housing can rise above the maximum permissible temperature. One way to decrease the head
transfer via thermowell is to install the transmitter further away from the heat source. Inversely
similar measurements can be done if the temperature gets below specified minimum
temperature.
.book Page 12 Friday, October 14, 2011 11:22 AM