Electrical connections, 3 electrical connection diagram – KROHNE PTD 600 EN User Manual

Page 12

Advertising
background image

4

ELECTRICAL CONNECTIONS

12

PTD 600

www.krohne.com

03/2012 - 4001946801 - MA PTD 600 R01 en

4.3 Electrical connection diagram

DANGER!
•

Check polarity and use shielded cables.

•

The transmitter housing and shield must be grounded.

•

Place the shielding on the control side to ground across a large area to ensure the best
possible protection against electromagnetic interference.
For field housing versions, place the shield evenly on the contact surface of the cable
feedthrough.

•

Avoid potential differences between the transmitter housing and the control if at all possible.
To comply fully with PELV requirements in accordance with EN 60204-1 §6.4.1, connect 0 V
(ground) to a point in the system with protective earth.

Figure 4-3: Electrical connection diagram

a: pressure transmitter
b: power supply / measuring unit

1 +V

S

(supply voltage)

2 I

Out

/GND (current output)

3 R

Load

4 Ground
5 Measurement
6 Operating voltage