Signal converter M10-EEx d – Supplementary instructions

11/2002

16

Physikalisch-Technische Bundesanstalt

PTB

Brunswick and Berlin


Schedule to EC Type Test Certificate PTB 01 ATEX 1154

(17) Special

conditions

none.

Additional directions for safe operation

Connection conditions
1.

The H…./…./M10-EEx variable-area flowmeter shall be connected up via suitable
cable glands and/or conduit systems that satisfy the requirements of EN 50018
Sections 13.1 and 13.2 and for which a separate test certificate is to hand.


2.

Cable glands and entry fittings (screwed conduit entries) as well as blanking plugs
of simple design may not be used. On connection of the H…./…./M10-EEx
variable-area flowmeter using a conduit entry approved for the purpose, the
associated sealing facility must be arranged directly on the housing.


3.

Unused openings shall be closed off as defined in EN 50018 Section 11.9.


4.

The connecting cable of the variable-area flowmeter shall be permanently installed
and in such as manner as to be adequately protected against damage.

These directions shall in suitable form accompany each apparatus.

Equipotential bonding
The H…./…./M10-EEx variable-area flowmeter shall be incorporated in the local
equipotential bonding system.

Permissible ambient and process temperatures as a factor of the temperature
class

Temperature

class

Ambient temperature in

°C

Max. permissible process

permanent temperature

Wiring Wiring Wiring

70°C 80°C 90°C

T6

-40 … +60

85

85

85

T5

-40 … +50

100

100

100

-40 … +60

85

100

100

T4

-40 … +50

135

135

135

-40 … +60

85 135 135

T3 ... T1

-40 … +40

180 200 200

-40 … +50

135 190 200

-40 … +60

85 145 200

The cable glands and line entries must have the same degree of thermal stability as the
connecting cable.