KROHNE OPTISOUND 3050C 4wire EN User Manual

Page 34

Advertising
background image

False signal suppression

Change now?

Proceed as follows:
1 Move from the measured value display to the main menu

by pushing [OK].

2 Select the menu item "Service" with [–>] and confirm with

[OK]. Now the menu item "False signal suppression" is

displayed.

3 Confirm "False signal suppression - Change now" with

[OK] and select in the below menu "Create new". Enter the

actual distance from the sensor to the product surface. All

false signals in this area are detected by the sensor and

saved after confirming with [OK].

Note:

Check the distance to the product surface, because if an

incorrect (too large) value is entered, the existing level will be

saved as false signal. The filling level would then no longer be

detectable in this area.

Additional adjustment and diagnosis options such as e.g.

scaling, simulation or trend curve presentation are shown in

the following menu schematic. You will find a detailed

description of these menu items in the operating instructions

manual of the indicating and adjustment module.

Optional settings

34

OPTISOUND 3050 C - 4 ... 20 mA/HART - four-wire

Setup with the indicating/adjustment module

30518

-EN
-050914

Advertising