Modbus protocol, 2 device status – KROHNE MFC 400 Modbus User Manual

Page 15

Advertising
background image

MODBUS PROTOCOL

5

15

MFC 400

www.krohne.com

05/2013 - 4002525102 - AD Modbus MFC 400 R02 en

5.8.2 Device Status

Modbus Function Codes "Read Discrete Inputs" (0x02)

Discrete
Inputs

Name

Description

Type

No. of
registers

Values

10000

10000

10000

10000

(0x2710)

Status of Custody

Transfer Lock

Indicates if custody transfer lock

is active or no

Bit

1

0 = unlocked

1 = locked

10001

10001

10001

10001

(0x2711)

Are Changes

Made?

Indicates if there are unsaved

changes. "Apply Changes" to

save them, "Discard Changes" to

work with previous settings

Bit

1

0 = no changes made

1 = unsaved changes

detected

Modbus Function Codes "Read Input Registers" (0x04)

Input
Register

Name

Type

No. of
registers

Values / Units

Display
Fct. No.

39000

39000

39000

39000

(0x9858)

Actual Operation Mode

Long

2

1 = Stop

2 = Startup

3 = Measuring

5 = Standby

B2.16

39002

39002

39002

39002

(0x985A)

Device Operation Time

Float

2

[s]

B2.1

39004

39004

39004

39004

(0x985C)

NE 107 Status Groups

Long

2

For further information refer to

NAMUR NE 107 Event Group(s)

on page 32.

-

39100

39100

39100

39100

(0x98BC)

NE 107 Device Status

Byte

1

Bit 7 = Failure (F)

Bit 6 = reserved

Bit 5 = Out of Specification (S)

Bit 4 = Function Check (C)

Bit 3 = reserved

Bit 2 = Maintenance required (M)

Bit 1 = reserved

Bit 0 = Information (I)

-