Transmitter-specific tables, 1 primary variable unit codes, 2 totalizer unit codes – KROHNE IFC 010 Converter HART User Manual
Page 28

HARTÆ Communications Protocol
IFC010 Command Specification Rev: 1.0
Release Date: 29 May 1997
© 1997 KROHNE Mefltechnik D-47058 Duisburg
Page
28
RESPONSE DATA BYTES
#0
#1
RS485
RS485
CONTROL
DEVICE
BYTE
ADDRESS
Data Byte #0
Bit-mapped control variable:
Bit #7..Bit #4 - RS485 baudrate:
0000 - м1200о
0001 - м2400о
0010 - м4800о
0011 - м9600о
0100 - м19200о
Bit #3..Bit #0 - RS485 mode:
0000 - ìOffî
0100 - ìKROHNE Protocolî
Data Byte #1
The device bus address in RS485-based network, valid settings: 0..249.
COMMAND-SPECIFIC RESPONSE CODES
0
No Command-Specific Errors
1-4
Undefined
5
Too Few Data Bytes Received
6-127
Undefined
9. Transmitter-Specific Tables
Refer to the Common Tables Document for all references in this section to ìSubset of Tableî.
9.1
Primary Variable Unit Codes
Subset of Table II, Unit Codes
24
liters/sec
17
liters/min
138
liters/hour
28
cubic meters/sec
131
cubic meters/min
19
cubic meters/hour
22
gallons/sec
16
gallons/min
136
gallons/hour
248
user defined
9.2
Totalizer Unit Codes
Subset of Table II, Unit Codes
40
gallons
41
liters
43
cubic meters