Technical data – KROHNE OPTIFLUX 1000 EN User Manual
Page 26

6
TECHNICAL DATA
26
OPTIFLUX 1000
www.krohne.com
04/2014 - 4000846303 - HB OPTIFLUX 1000 R03 en
Operating conditions
Temperature
Temperature
Temperature
Temperature
Process temperature
-25...+120°C / -13...+248°F
Ambient temperature
-25…+65°C / -13…+149°F
Protect electronics against self-heating at ambient temperatures above
+55° C / +131°F
Storage temperature
-50…+70°C / -58…+158°F
Measurement range
Measurement range
Measurement range
Measurement range
-12...+12 m/s / -40...+40 ft/s
Pressure
Pressure
Pressure
Pressure
Ambient pressure
Atmospheric
Operating pressure
Up to 16 bar / 230 psi
Vacuum load
0 mbar / psi absolute
Pressure loss
Negligible
Pressure ranges for
secondary containment
Pressure resistant up to 40 bar / 580 psi
Burst pressure up to approx. 160 bar / 2320 psi
Chemical properties
Chemical properties
Chemical properties
Chemical properties
Physical condition
Electrically conductive liquids
Electrical conductivity
Standard: ≥ 5 μS/cm
Demineralized water: ≥ 20 μS/cm
Permissible gas content
(volume)
IFC 050: ≤ 3%
IFC 100: ≤ 3%
IFC 300: ≤ 5%
Permissible solid content
(volume)
IFC 050: ≤ 10%
IFC 100: ≤ 10%
IFC 300: ≤ 70%
Installation conditions
Installation
Assure that the flow sensor is always fully filled.
For detailed information refer to
Installation
on page 12
Flow direction
Forward and reverse
Arrow on flow sensor indicates positive flow direction.
Inlet run
≥ 5 DN
Outlet run
≥ 2 DN
Dimensions and weights
For detailed information refer to
Dimensions and weights
on page 30