ALTOSONIC

III

18


BOTH (forward and reverse flow measurement indicating both in the same range)
F/R SPEC (forward and reverse flow measurement indicated in different range see Function 3.04.04)

3.04.03

RANGE

Range of current output
OTHER (user defined, see Function 3.04.04 through 3.04.06)
0-20/22 mA (0 pct - 100 pct / limit)
4-20/22 mA(0 pct - 100 pct / limit)

3.04.04

0 pct

Current value for 0% scale
Range: 0 through 16 mA

3.04.05

100 pct

Current value for 100% scale
Range: 4 through 20 mA
Value must be at least 4 mA greater than current value for 0% scale

3.04.06

LIMIT

Limitation of current value
Range: 20 through 22 mA

3.05.00

PULSE OUTP

Submenu 3.05.00 Pulse output

3.05.01

FUNCTION

Function of pulse output
OFF (switched off)
ACT FLOW (actual flow)
VOS (velocity of sound, range defined in Function 3.01.11 and 3.01.12)
GAIN (sensor signal gain, range is 0 dBV through 100 dBV)

3.05.02

DIRECTION

Direction of pulse output
FORWARD (forward flow measurement)
BOTH (forward and reverse flow measurement indicating both in the same range)

3.05.06

TIME CONST

Time constant of pulse output
25 ms
MASTER TC (see Function 3.01.04)

3.05.07

OUTPUT

Unit of pulse output (see Function 1.03.00)
PULSE FREQUENCY, pulses per unit time, see Function 3.05.08)
PULSE/UNIT, Totalizer pulse output, pulses per unit volume, see Function 3.05.09

3.05.08

PULSE RATE

Pulse rate (frequency) value for 100 % scale
pulse/s, pulse/hr, pulse/min
Range: 1 pulse/hr through 2000 pulse/s

3.05.09

PULSE/UNIT

Pulse value per volume unit for totalization
pulse/m³, pulse/l, pulse/US Gal, pulse/bbl,
free user definable unit

3.06.00

DIG INPUT

Submenu 3.06.00 Digital input

3.06.01

FUNCTION

Function of digital input
OFF (switched off)
RST ERROR (reset error messages)

3.07.00

USER DATA

Submenu 3.07.00 User data

3.07.01

LANGUAGE

Language for display texts
GB/USA (English)
D (German)
F (French)

3.07.02

ENTRY CODE

Entry code for setting mode
NO (entry with key only)
YES (entry with key and code 1, factory set on 9 x key, see Function 3.07.03)

3.07.03 CODE

1

Code

1

Press any 9-keystroke combination and then press the same combination again. Each keystroke is
acknowledged by "Ж" in the display. If both combinations are equal, "CODE OK" appears and the new
code can be stored, else "WRONG CODE" appears and the desired code has to be entered again.

3.07.04 LOCATION

Tag

name

setting

Free settable tag for identification, maximum 10 characters.
Characters assignable to each place: A..Z / blank character / 0..9
Factory setting: KROHNE

3.07.05

UNIT TEXT

Text for user-defined unit
Definition: volume/time
Characters assignable to each place: A..Z / blank character / 0..9
Fraction bar "/" in 5th place is unalterable
Factory setting: XXXX/YYY

3.07.06

UNIT VOL

User-defined unit volume
Quantity of user-defined volume per m³.
Range: 10-5 through 107
Factory setting: 1

3.07.07

UNIT TIME

User-defined unit time
Amount of user-defined time in seconds
Range: 10-5 through 107
Factory setting: 1