Examples, 1 level measurement mode (pr.1 = 1) – KROHNE BM 90 EN User Manual
Page 27

27
4. Examples
4.1 Level measurement mode (Pr.1 = 1)
Applications for this mode are Level Measurement, Contents Measurement and Pump Control.
The application :
l
To measure and display the level of liquid in meters
l
Maximum level 3 m,
l
Fill rate 0.1 meter/min
l
Alarm if level exceeds 2.8 m
l
0-20 mA signal proportional to level
Pr. 1
=
1
Defines level measurement.
Pr. 2
=
2
Programme units are meters.
Pr. 3
=
4
Distance of transducer from the zero level.
Pr. 4
=
3
The span, based on zero level.
Pr. 5
=
0.5
Blanking zone into which level should not rise.
Pr. 6
=
0.1
The maximum rate of change of liquid level in meters/min.
Pr. 8
=
1
Relay 1 to alarm on level (normally energised).
Pr. 9
=
2.8
Relay 1 de-energised at 2.8 m indicates high alarm.
Pr.10
=
2.6
Relay 1 re-energised at 2.6 m to clear the high alarm.
Pr.23
=
3
Hold alarm indication (relay 1) on failsafe.
Pr.28
=
3
Analogue output holds on failsafe.
Pr.30
=
3
0.20 mA output fixed to span (Pr.4).
Pr.78
Simulate the program.
3.0m
(Pr.4)
4.0m
(Pr.3)
Reset
Alarm
2.8m
(Pr.9)
Set
Alarm
0.5m
(Pr.5)
2.6m
(Pr.10)