 -400msforfinalcircuitsnotexceeding32A(at230/400VAC)

 -5sfordistributioncircuitsandcircuitsover32A(at230/400VAC)

The compliance with the above rules shall be verified by:

1)MeasurementofthefaultloopimpedanceZsbyLooptester.

2) Verification of the characteristics and/or the effectiveness of the

associated protective device. This verification shall be made:

- for circuit-breakers and fuses, by visual inspection (i.e. short time

or instantaneous tripping setting for circuit-breakers, current rating
and type for fuses);

-for RCDs, by visual inspection and test using RCD testers

recommending that the disconnecting times mentioned above are

met(PleaseseeRCDTESTsection).

ForinstanceinaTNsystemwithnominalmainsvoltageUo=230

V protected by General purpose gG fuses or MCBs (Miniature

CurrentBreakers)requiredbyIEC898/EN60898,theIaandmax

Zs values could be:

ProtectionbygGfuses

with Uo of 230V

ProtectionbyMCBswithUoof230V

(Disconnectiontime0.4and5s)

Rating

(A)

Disconnection

time 5s

Disconnection

time0.4s

Characteristic

B

Characteristic

C

Characteristic

D

la(A)

Zs(Ω) la(A) Zs(Ω) la(A) Zs(Ω) la(A) Zs(Ω) la(A) Zs(Ω)

6

17

13.5

38

8.52

30

7.67

60

3.83

120

1.92

10

31

7.42

45

5.11

50

4.6

100

2.3

200

1.15

16

55

4.18

85

2.7

80

2.87

160

1.44

320

0.72

20

79

2.91

130

1.77

100

2.3

200

1.15

400

0.57

25

100

2.3

160

1.44

125

1.84

250

0.92

500

0.46

32

125

1.84

221

1.04

160

1.44

320

0.72

640

0.36

40

170

1.35

--

--

200

1.15

400

0.57

800

0.29

50

221

1.04

--

--

250

0.92

500

0.46 1000 0.23

63

280

0.82

--

--

315

0.73

630

0.36

1260

0.18

80

403

0.57

--

--

100

548

0.42

--

--

The most complete loop testers or Multifunction testers also

have the Prospective Fault current measurement. In this case,

Prospective Fault current measured with Instruments must be

higher than the tabulated Ia of the protective device concerned.

BelowisapracticalexampleofverificationoftheprotectionbyMCB

inaTNsystemaccordingtotheinternationalStandardIEC60364.