● Operating Error

Operating error (B) is an error obtained within the rated operating

conditions, and calculated with the intrinsic error (A), which is an

error of the instrument used, and the error (Ei) due to variations.

According to IEC61557, the maximum operating error should be

within ±30%.

● Operating error at earth resistance measurements (IEC61557-5)

Formula: B= ±(|A|+1.15 x √E

2

2

+E

3

2

+E

4

2

)

A

Reference condition

E

1

Normal operating position ±90º

E

2

Variation due to changing the supply voltage (until the

Battery symbol

appears)

E

3

Variation due to changing the temperature

(-10ºC to 50ºC)

E

4

Variation due to series interference voltage

16•2/3Hz, 50Hz, 60Hz, DC: 10V

400Hz: 3V

E

5

Variation due to resistance of the probes and auxiliary

earth electrode resistance

E

1

: It is not applicable to digital testers.

E

5

: It is not applicable to simplified earth testers.

Measurement range within which the maximum operating error

±30% applies: 5.00Ω to 2000Ω.

● Number of measurement

(measuring for 5 sec and take a pause for 25 sec)

Function

Resistor

for test

Number of measurement

(within effective battery voltage

range)

Earth measurement 10Ω

Approx. 3000 times