NOSHOK 624 Series Pressure Transmitters User Manual

Pressure transmitters, User manual noshok, Non-incendive

Advertising
background image

model 624 has G1/2B or G1B flush diaphragm

connections. Refer to the catalog for complete

specifications. Do not torque the process connector

with a force greater than 37 foot pounds.

For the 4 mA to 20 mA output version, install

the power supply, transmitter and receiving

instrument in series to form a 2-wire current

loop. The transducer regulates the current in

the loop.

The transmitter is classified for over-voltage

category II and the pollution degree 1. For the

voltage output version, the 3-wire system uses

separate leads for the power supply and output

signal. The 3rd lead is a common minus.

Use a NEC Class 02 power supply, low

voltage and low current maximum 100 VA even

under fault conditions.

Maintenance

NOSHOK series 623 and 624 non-incendive

pressure transmitters require no maintenance.

The are calibrated at the factory using pressure

standards traceable to N.I.S.T. There are no user

available adjustments.