Troubleshooting, Calibrating the display, Decimal point position selection – NOSHOK 1900 Series Current Loop Powered Process Indicators User Manual

Page 4: Application example

Advertising
background image

CALIBRATING THE DISPLAY

Calibrating the 1900C unit requires either an accurate adjustable constant

current supply or the 1900C unit can be installed and scaled with the process

sensor connected to the 1900C unit. To calibrate the unit, proceed as follows.

1. Set DIP switching for the desired current range.

2. Select the desired decimal point position.

3. Apply the minimum input signal to the 1900C unit and adjust the

COARSE OFFSET to display the approximate desired minimum value.

4. Apply the maximum input signal to the 1900C unit and adjust the

COARSE SPAN to display the approximate desired maximum value.

5. Repeat steps 3 and 4 until the minimum and maximum values are within the

desired values.

6. Apply the minimum input signal to the 1900C unit and adjust the FINE

OFFSET to display the exact desired minimum value.

7. Apply the maximum input signal to the 1900C unit and adjust the FINE

SPAN to display the exact desired maximum value.

8. Apply the minimum input signal and verify that the display indicates

correctly.

9. Apply the maximum input signal and verify that the display indicates

correctly.

10. Repeat Steps 6 through 9 until display reads exact.

Note: The 1900C Unit display is factory calibrated to indicate 0.0 to 100.0

with an input of 4 to 20 mA at approximately 25°C.

BLOCK DIAGRAM

DECIMAL POINT POSITION SELECTION

The decimal point position is DIP switch selectable for one of three locations.

The 1900C unit can be set up to read in 10ths, 100ths, or 1000ths. If all the

DIP switches are set to the “OFF” position, no decimal point will appear on the

display. The DIP switches are located at the rear of the unit.

APPLICATION EXAMPLE

Operation of a refinery process required a local display of the position of a

remote pipeline valve. The display would indicate 0 (zero) when the valve was

fully closed with an input signal of 4 mA. When the valve was fully open the

display would indicate 100 with an input signal of 20 mA.

Both the 1900C-1/1900C-2 and the 1900C-3/1900C-4 meet the necessary

TROUBLESHOOTING

For further technical assistance, please contact us.

1900C-2

requirements.

TM190004-1

Corporate Headquarters

1010 West Bagley Road

Berea, Ohio 44017

Ph: 440.243.0888

Fax: 440.243.3472

E-mail: [email protected]

Web: www.noshok.com

INCORPORATED

Advertising