6.5 MODULE 5 - S

ERIAL

S

ETUP

P

ARAMETERS

(

5-SEr

)

The Serial Setup Parameters are only active when the optional RS232 or RS485 serial communications module is installed in the meter.

PARAMETER MENU

button or user input manual reset, serial reset command or meter power
cycle. When the user input or

RST

button is activated (momentary action),

the corresponding “on” output is reset immediately and remains off until the
trigger point is crossed again. (Previously latched alarms will be off if power
up Display Value is lower than setpoint value.)

L-dLY

= Latch with delay reset action; This action latches the output on at the

trigger point per the Setpoint Action shown in Setpoint Output Figures. Latch
means that the output can only be turned off by the front panel

RST

button

or user input manual reset, serial reset command or meter power cycle. When
the user input or

RST

button is activated (momentary action), the meter

delays the event until the corresponding “on” output crosses the trigger off
point. (Previously latched outputs are off if power up Display Value is lower
than setpoint value. During a power cycle, the meter erases a previous

L-dLY

reset if it is not activated at power up.)

Setpoint Output Reset Actions

This parameter enables the

RST

button or user input to reset the output when

the display is reset.

Note: For this parameter to operate, the

RST

button or User Input being used

must be set to

dSP

and the Input value must be displayed. If these conditions are

not met, the output will not reset.

ª

«

YES

rEn-n

OUTPUT RESET WITH DISPLAY RESET

YES

NO

When

YES

, the output is disabled (after a power up) until the trigger point is

crossed. Once the output is on, the output operates normally per the Setpoint
Action and Output Reset action.

ª

«

NO

Stb-n

STANDBY OPERATION

YES

NO

This parameter enables the backlight 1950 to switch the backlight color when

the output state changes. This parameter is only active for the backlight version.

CHANGE DISPLAY COLOR w/OUTPUT STATE

ª

«

NO

ChC-n

YES

NO