MODEL 1022 & 1025

7

05/10/2007

TROUBLE SHOOTING

CAUTION: High voltage exists on the supply and load terminals of this controller and may exist on other equipment

located near the controller. Use extreme caution to avoid electrical shock.

The LED located on the controller circuit can be used to aid in determining problems. This LED varies in intensity

proportional to the command signal and therefore should be proportional to the load voltage.

THE FOLLOWING ARE SYMPTOMS AND POSSIBLE CAUSES:

SYMPTOMS

POSSIBLE CAUSES

NO LOAD POWER, LED not ON:

Determine that the command sigal is applied to the

controller. Determine that 24 volts is applied to the circuit.

NO LOAD POWER, LED intensity can be varied:

Determine that all fuses are “OK”. If the voltage across the

SCR module is equal to the line voltage the SCR module

has probably failed. NOTE: If a replacement SCR module

is ordered specify the voltage and current rating of the

controller and the serial number of the failed unit.

LOAD POWER IS MAXIMUM AND CANNOT BE

REDUCED, LED is ON:

Determine that the command signal can be adjusted to

zero. Also remove the green plug-in connector to remove

the command signal. If the LED is not off, the circuit card

has failed.

LOAD POWER IS MAXIMUM AND CANNOT BE

REDUCED, LED is OFF:

Remove the 24Vac plug in connector. If the load still has

power the SCR module has probably failed as a short

allowing full power at be applied to the load. To determine

if the SCR module has shorted remove power and then

the line and load connections and measure the resistance

across the line and load terminals on the SCR module. If

the resistance is less than 10000 ohms the modual has

failed. NOTE: If a replacement SCR module is ordered

specify the voltage and current rating of the controller and

the serial number of the failed unit.

LOAD VOLTAGE SNAPS ON:

Determine that the primary of the circuit transformer is

connected to the same supply as the controller and load.

MAXIMUM LOAD VOLTAGE CANNOT BE OBTAINED:

Determine that the primary of the circuit transformer is

connected to the same supply as the controller and load.

Typically this problem is caused by the primary being

connected across the load and line connection at the

controller.