MODEL 1022 & 1025

1

05/10/2007

DESCRIPTION

The models 1022 and 1025 are single-phase phase-angle SCR power controllers. The controllers are the same except

the 1022 accepts command signals of 0/5Vdc, 0/10Vdc or a potentiometer signal. The model 1025 accepts a 4/20mA

command signal.

Both controllers control the RMS voltage to the load proportional to the command signal, independent of line voltage

hanges. The controllers include soft-start and missing cycle detection which on power interruptions of one half cycle or

more sets the load voltage to zero and then increases the load voltage to the desired voltage at a predetermined rate.

his eliminates inrush currents that can occur due to loads with a low cold resistance or because of saturation when a

transformer is used between the controller and the load.

The command signal is electrically isolated from line and load voltages and all are electrically isolated from the heat sink.

SPECIFICATIONS

CONTROL MODE:

Single-phase; Phase-angle; RMS value of the voltage applied to the load

COMMAND SIGNAL:

SIGNAL INPUT IMPEDANCE

Model 1022 0/5 Vdc 100K

0/10 Vdc 200K

Potentiometer 200K

(1K pot recommended, 20K permissible)
Model 1025 4/20 mA 200 Ohms

CONTROL RANGE:

6 to 97% of line voltage typical.

LINEARITY:

RMS load voltage is linear within 2% of span of the command signal.

ZERO AND SPAN

ADJUSTMENTS:

User adjustable over range of +/- 20% of span.

ISOLATION:

Dielectric strength input/line & load voltage/heatsink 4000V (RMS).

Insulation resistance input/line & load voltage/heatsink 10^10 ohms.

Maximum capacitance input to output 8pf.

COOLING:

Convection

MOUNTING:

Must be mounted on vertical surface with fins vertical. Unit may be mounted

adjacent to each other. Heatsink is electrically isolated.

LINE VOLTAGE:

120, 240, 480 or 575 Vac +10%, -20% 50/60 Hertz

DIAGNOSTIC INDICATOR:

The intensity of an LED varies as a function of the command signal. Feature

provides a quick and safe means to check controller operation.

PHYSICAL:

Weight: 10 - 40 Amp 2 lbs 70 Amps 6 lbs

Dimensions: Refer to installation drawings.

ENVIRONMENT:

Operating: 0 to 55° C (32 to 131° F)

Storage: -40 to 80° C (-40 to 176° F)

Humidity: 0 to 95% Non-condensing

DV/Dt AND TRANSIENT

VOLTAGE PROTECTION:

200 volts/usec minimum

A dv/dt snubber and a metal oxide varistor (MOV) are provided to protect against

high frequency transients (dv/dt) and voltage spikes.

DISSIPATION:

1.5 watt per amp of controlled current

RECOMMENDED FUSING:

Special semiconductor fuses are not required. It is advised that the controller and

load be protected with fast acting class ‘T’ fuses such as Bussmann type JJN (300V)

or JJS (600V) fuses. Control Concepts maintains an inventory of fuses and fuse

holders for your convenience. It is recommended that a fuse rated 120 to 125% of

maximum load current be selected.