Seametrics PE102 User Manual

Page 3

Advertising
background image

+

_

S

+

_

+

_

+

_

INSTALLATION and CONNECTIONS

INSTALLATION

Positioning.

The PE102 can be mounted vertically or horizon-

tally. It is important to choose a position that will ensure full

pipe. (Under certain conditions of empty or partially-full pipe

the meter may give a pulse out when there is no flow.) With a

zero straight pipe requirement after an elbow, the PE meter

can be installed in tight spaces.

Mounting.

The PE102 may be supported by its piping connec-

tions IF the piping is rigid. The meter and pipe must be per-

fectly aligned with no flexion at the fittings to prevent damage

to the meter and leakage. It is highly recommended to use the

mounting bracket provided. The mounting bracket uses two #8

screws on a 1.5” center.

Piping.

Metal pipe, metal tube, or plastic tubing can be used

with the meter. The standard FlareTek fittings can be used with

or without NPT adapters on 3/4” or 3/8” pipe. If used, NPT

adapters should be hand-tightened onto the fittings to avoid

damage to internal O-ring seals. Thoroughly clean the pipe

threads and nose and apply Teflon tape to adapter threads.

Hold fittings/adapters with a wrench while tightening the pipe

to prevent damage to the meter. If using FlareTek fittings, fol-

low the installation instructions provided with your flare tool.

Power Supply.

A 12 Vdc linear, regulated power supply with an

output current of at least 0.25A is recommended. If a switching

power supply must be used, consult Seametrics for approved

manufacturer’s model numbers.

CONNECTIONS

Power and signal connections are provided through the 8-pin

male bulkhead connector on the meter housing (20ft (6m)

cable provided). See the Pin Assignment and Connections

diagrams below.

In addition, it is necessary for proper operation to ground the

unit to a good quality earth ground. Assure negative power

supply is grounded to earth and to the entire electrical/me-

chanical system. If metal piping is used, jumper inlet and

outlet pipes together and connect to ground for best results

in metering accuracy.

2

1

3

7

4

6

5

8

+

_

SEN 1

SEN 2

+

_

12

G

Pin8

Pin2

Pin3

FT520

12 Vdc

power

PE102

Sensor Input

FT420

Power

1

PE102

4-20 mA Device and FT420 with Single Power Supply

Dual Power Supply with Loop Isolation

Pin# Function Color

1

Pulse (-)

White

2

Ground

Brown

3

Pulse (+)

Green

4

4-20 (+)

Yellow

5

Not Used

Grey

6

Not Used

Pink

7

4-20 (-)

Blue

8

Power (+)

Red

Pulse Output Only with FT520

12-15

Vdc

4-20

device

4-20 mA

loop

2

3

4

8

7

+

_

S

+

_

+

_

+

_

+

_

FT420

PE102

12-24

Vdc

4-20

device

4-20 mA

loop

12-15

Vdc

Sensor Input

Power

1

2

3

4

8

7

Cable Plug Contact

Arrangement

Pin1