Installation

Wall Mounting. Using the eight screws provided, attach
the two foot brackets to the sides of the enclosure. Then
attach the unit to any secure surface by inserting screws
through the mounting holes in the foot brackets.

Panel Mounting. Follow the dimensions for “Panel
Cutout” to cut a hole in the panel. Slide the panel mount
gasket up from the bottom of the enclosure to its place
behind the panel mount flange. Insert the unit through
the panel cutout. Install the two panel mount brackets
on the sides of the unit using the eight screws provided.
Each bracket has one threaded center hole. Insert and
tighten one screw in each hole, until the flange is pulled
firmly up against the panel and the gasket is compressed.

Expose Terminals. Remove the four screws which hold
the front plate to its flange. Remove the front plate. The
display board is attached to this front plate. It is also
connected to the power board by a ribbon cable. For
convenience, this cable can be disconnected, or the
display board can be allowed to dangle while making
connections. Connections can be made inside the
enclosure, or the terminals can be unplugged for easier
access, by gently tugging on them.

Sensor Connection. Follow the “Connections” diagram
to connect either two or three wires from the flow meter
or flow sensor.

Batch Control Connection. Connect the valve or other
device(s) to be controlled for starting and stopping the
batch to the appropriate relay terminals. Note: if the
staged shutoff (“prewarn”) will not be used, connect to
relay one only. Relay 1 remains energized for the entire
batch cycle. If a staged shutoff is desired, connect the
main valve to Relay 2 (early shutoff) and the low-flow
valve to Relay 1.

Power Connection. Connect AC or DC power as
desired to the appropriate terminals. For safety, if using
AC power, be sure to connect the ground terminal
provided to a good earth ground.

2 of 4

Displays

Settings

Batch Setting. These functions are covered under
operation. When first setting up the FT520, skip down to
Flow Rate and K-Factor, which must be set before
batching can be done.

Set Flow Rate. Use

to select volume units. Use

to select the particular unit desired (gallons, liters, etc.).
Then use

to switch to time units. Again, select the

one desired.

Set Decimal. Use

to select zero, one, or two decimal

places on the flow units.

Set K-Factor. The unit will not function properly until
this number is entered. It is simply the number of pulses
which the flow meter or flow sensor puts out per gallon
of liquid. It is marked on the Model/Serial tag of
SeaMetrics flow meters and flow sensor fittings. On
adjustable flow sensors, the K-factor must be taken from

Caution: When the control is
powered up, relay or analog out-

puts may be present. If this
could be a hazard, wait to make
external connections until pro-

gramming is complete.

!

Replace the front panel, taking care to reconnect the
ribbon cable if it has been disconnected. When power
is switched on, the display should light up immediately
with meaningful letters or digits.

0 GPM

0 GPM

O GAL

0 GPM

O GAL

B

T

SETTINGS

OPERATION MODE

SET BATCH SIZE

123 GAL

SET

SET

SET PREWARN SIZE

123 GAL

SET

SET

SET

SET

SET

SET

SET

SET DECIMAL

0.00 GPM

SET K-FACTOR

123.456

SET PULSE OUT

123 GAL

TO CLEAR TOTAL

PRESS UP & LEFT

SET 20mA RATE

0.00 GPM

GAL

MINUTE

FLOW
RATE

return to
operation mode

Bar
Graph

Batch

Running
Totalizer