Manual operation and override, Override, Automatic stroke adjustment – Warren Controls PICV Series User Manual

Page 16: Reset, Control signals, Set-up, Switch functions

Advertising
background image

16

2600 Emrick Blvd • Bethlehem, PA 18020 • USA • 800-922-0085 • www.warrencontrols.com

When the actuator settings are known, it is easier to make them
before the valve and actuator are installed in the system. When
power is first applied to the actuator, check to see that it moves
through its full range. If it does not, reset it by moving switch #9.

MANUAL OPERATION AND OVERRIDE

The actuator can be manually operated with a metric hex wrench. The
VM1500E uses a 4mm hex wrench. The VM5000E uses an 8mm hex
wrench. The socket is on top of the actuator. VM5000E actuators have
a clutch button that must be depressed while manually operating the
actuator. De-Energize the actuator before manual operation.

OVERRIDE

:

Connecting the neutral (terminal SN) to terminal 1 lowers the stem
and to terminal 3 raises the stem. This can be done by an external
switch or controller.

AUTOMATIC STROKE ADJUSTMENT

The stroke adjusts itself automatically. This happens the first time
power is applied or whenever the position of switch #9 is changed.

Adjustment takes several minutes during which the actuator will
move through its full stroke 2 or 3 times. The actuator remembers the
settings so a power failure does not cause the actuator to reset itself.
The automatic stroke adjustment does not work if the valve stroke
is greater than the limits of the actuator. The maximum strokes are:

VM1500E 1 1/2” 40 MM

VM5000E 2 1/8” 55 MM

Automatic stroke adjustment ensures that the signal range covers
the actual stroke of the valve.

RESET

Changing the position of switch #9 makes the actuator recalculate
the stroke. Do this if the actuator has been used on another valve,
tested without being on the valve, has been incorrectly mounted on
the valve, or has been taken off of the valve and reinstalled.

CONTROL SIGNALS

The actuator must be set for the control signal being used and
whether the signal is direct acting or reverse acting.
The acceptable signals are:

24 VOLTS AC 3

POINT

FLOATING

or any of the following proportional signals.

24 volts ac

Terminal 1 Stem down

Terminal 3 Stem up

Feedback Positive

0 - 10 or 2 - 10 Vdc

Control signal

Positive

24 volts ac

Common and control signal negative

If system is grounded, then ground SN

SET-UP

SP ........................ 24 volts AC power in

SN ....................... Common (Ground) and control signal negative

(See wiring diagrams)

Y .......................... Control signal in (Positive)

X .......................... Feedback signal out (Positive)

1 .......................... Override

3 .......................... Override

SWITCH FUNCTIONS

Switch OFF

ON

1

Voltage Control Signal

Milliamp Control Signal

2

2 - 10 Volts or 4 - 20 ma

0 - 10 volts or 0 - 20 ma

3

Direct Acting

Reverse Acting

(Extend on increasing signal)

(Retract on increasing signal)

4

Full Range

Split Range

5

Low Range Signal

High Range Signal

6

Proportional

3 Point Floating

7

Equal Percentage Valve (Default)

Linear Valve

8

(Default)

DO NOT USE

9

Reset

Reset

In the override position the Actuator is driven

to the end position. Connecting to terminal

1 drives the stem down. Connecting to

terminal 3 drives the stem up.

24 volts ac

Common and

control signal negative

Override