VALVE BODIES

Body Material:

Cast Iron

End Connections:

ANSI 125LB FF Flanges, PN16 FF Flanges

Trim Designs:

Type 23 - Single Seat Cylinder Balanced, ANSI Class III Leakage

Type 22 and 72 - Double Seat Balanced, ANSI Class III Leakage

Trim Material:

Bronze or 300 Series Stainless Steel

EPDM Seal (Type 23 w/Bronze Trim)

Fluoraz Seal (Type 23 w/Stainless Steel Trim)

Fluid:

Chilled Water Typical, Water or Water/Glycol from 35 °F- 180°F (2°C - 82°C )

Trim Limits:

Stainless Steel: MAX Flowing Differential Pressure, 150 PSIG (10.3 BARG)

Bronze: MAX Flowing Differential Pressure, 100 PSIG (6.9 BARG)

Packing:

Long-Life Multi-Stack EPDM Lip Packing - Water / Water-Glycol Service

ELECTRIC ACTUATOR SPECIFICATIONS

(VM-1500E AND VM-5000E)

Valve Usage:

VM-1500E [Valve sizes 2 1/2, 3 & 4 Inch DN65, DN80 & DN100],

VM-5000E [Valve sizes 5, 6, 8 & 10 Inch DN125, DN150, DN200, DN250]

Control Signal:

4-20 mAdc (Factory Setting), 0-20 mAdc, 0-10 Vdc or 2-10 Vdc

and Floating, Self-Adjusting, Field Selectable (Dip Switch)

Power Consumption: VM-1500E 12VA, VM-5000E 25VA

Timing:

VM-1500E [102 sec. / inch, 4.02 sec. / mm], VM-5000E [76 sec. / inch, 2.99 sec./mm]

Feedback Signal:

4-20 mAdc (Factory Setting), 0-10 Vdc or 2-10 Vdc

Failure Mode:

Fail-As-Is [Without VMS-25 BCM (Back-up Control Module)]

Fail-Safe [With VMS-25 BCM (Back-up Control Module)]

Manual Override:

Yes

Construction:

Polycarbonate Motor Housing with Steel Linkage & Yoke.

Case has one 1/2 inch (1.27 cm) NPSM Conduit Adapter

Connections:

Coded Screw Terminals

Locations:

NEMA Type 3 / IP54

Temperature Limits:

Ambient 32°F - 122°F ( 0°C - 50°C )

Mounting:

Factory Aligned, Vertical Above Centerline of Control Valve

Consult factory for preconfigured alternate orientations

VMS-25 BCM

(BACK-UP CONTROL MODULE)

SPECIFICATIONS

Actuator Usage:

VM-1500E & VM-5000E

Required for Fail Safe Operation
Failure Direction:

Field Selectable

Power Consumption: 24VAC, 40VA
Construction:

Battery w/Circuit Board & Transformer, in Nema 4 Enclosure

Mounting:

Wall Mount

Weight:

4.25 lbs (2 kg)

Body Pressure Temperature Ratings

Iron Body

Temperature

125 FLG & PN16

O

F

O

C

PSIG BARG

35 to 180 1.7 to 82.2

150

10.20

CONFIGURATIONS

Control

Valve

Size

Control

Valve

Flange

Control

Valve

Profile

Control

Valve Trim

Size

Control Valve

Trim Material

Control Valve

Motor

DPRV

Size

DPRV

Flange

DPRV

Trim

Material

DPRV Actuator

0

ANSI 125

Flanges

2

PN16

Flanges

22

Type of

Control
Valve
Body
(Sizes P8
& P1)

23

Type of

Control
Valve
Body
(Sizes
P2-P6)

F

Control Valve
Trim Size Ful

l

X

Control Valve
Trim Size
Extended

1

Control Valve
Trim Size 1SR

2

Control Valve
Trim Size 2SR

S

Stainless Steel

B

Bronze

E020

VM1500E -

Fail As Is

E021

VM1500E - w/

VMS-25
BCM

E022

VM5000E -
Fail As Is

E023

VM5000E - w/

VMS-25
BCM

TIG1

TR5000-X

-Fail As Is
for all exceot
P6_23XX
Extended Port

TIG2

TR5000-X

-Fail As Is
Extended Port
Only

0

ANSI 125

Flanges

2

PN16 Flanges

Note: Must
match control
valve

DS

DPRV Type

72 Portion
w/ SS Trim

DB

DPRV Type

72 Portion
w/ Brz
Trim

2L

DPRV Actuator Cast
Iron, w/ Low DP Spring

2M

DPRV Actuator Cast
Iron, w/ Medium DP
Spring

P2

2.5” DN65

P3

3” DN80

P4

4” DN100

P5

5” DN125

P6

6” DN150

P8

8” DN200

P1

10” DN250

P2

2.5” DN65

P3

3” DN80

P4

4” DN100

P5

5” DN125

P6

6” DN150

P8

8” DN200

P1

10” DN250

Advertising