F3 & f4 motors, F5 & f6 motors, Wiring supply, signal and feedback – Warren Controls AmurAct Actuator Linkage and Motor User Manual

Page 7

Advertising
background image

7

AmurAct

IOM_AA_RevH_0413

WIRING SUPPLy, SIGNAL AND FEEDBACk

SUPPLY VOLTAGE

Locate the green case-grounding wire inside the motor case and connect it to the earth ground lead from the

power source. Connect the neutral (typically white) wire to terminal one (1) on terminal block TB5. Connect

the “hot” (typically black) wire to terminal two (2).

1 2

TB5

Neutral

liNe

120 Vac

f3 & f4 mOTORS

120 VAC (Single-phASe 50/60 hz)

Locate the green case-grounding

wire inside the motor case and

connect it to the earth ground lead

from the power source. Connect

one “hot” wire to each of the two

terminals on terminal block TB5.

1 2

TB5

liNe

liNe

220 Vac

earth grouNd

f5 & f6 mOTORS

220 VAC (Single-phASe 50/60 hz)

1 2

TB1

CoMMoN (-)

(liNe)

24 VAc OR 30 VDc

3 4 5

If the actuator is to be powered by 24 vAC or 30 vDC, connect the negative or common wire to termi-

nal ONE (1) and the positive (or "hot" wire) to Terminal TWO (2) on TB1. When powered by (24 vDC,

Special Consideration) voltage, motor torque will be reduced by approximately 10% which will reduce

close off capability. Contact the factory for questions.

f3 & f4 mOTORS

24 VAC or 30 VDC

CONTROL SIGNAL - Current (milliamp) <DEFAULT>

If the control signal is 4 - 20 mA, connect the control wires to TB1 as shown below. Dip-

switch #3

MUST be in the ON position.

1 2

TB1

CoMMoN (-)

(+) CoNtrol 4-20 Ma dC

3 4 5

earth grouNd

(24 VDc - W / Special considerations)

Advertising