For 2-way only, Dipswitches, Feedback signal – Warren Controls AmurAct Actuator Linkage and Motor User Manual

Page 8: Control signal - voltage, Configuration of dipswitches

Advertising
background image

FEEDBACK SIGNAL

This signal is an output signal and not required for operation. The sole function is to provide a verified feedback signal that is proportional to rotation.

The actuator can be set to provide a 4-20 mA feedback signal (factory default) or a 2-10 vdc feedback signal. For 4-20 mA feedback dipswitch #4 must be

in the OFF position. For 2-10 vdc feedback, dipswitch #4 must be in the ON position. Connect the feedback wires to TB1 as shown below. If the actuator

is set for CCW rotation on increasing signal (factory default) and the actuator is at 90º rotation (facing the motor) the feedback will be 4 mA or 2 vdc, at

45 degrees rotation the feedback will be 12 mA or 6 vdc and at 0º

rotation (facing the motor) the feedback will be 20 mA or 10 vdc. If

the actuator is set for CW rotation on increasing signal the direction

of the feedback signal will be reversed.

CONTROL SIGNAL - Voltage

If the control signal is 2 - 10 vdc, connect the control wires to

TB1 as shown. Dipswitch #3

MUST be in the OFF position.

CONFIGURATION OF DIPSwITCHES:

Factory default configuration of the five dipswitches is shown below.

Switch #1

Factory default - ON

An increasing control signal causes the valve

stem to drive up, opening a two-way valve, or opening the L (lower) port and

closing the U (upper) port of a three-way valve. The valve stem will drive down

upon loss of signal. When Switch 1 is in the OFFposition an increasing control

signal causes the valve stem to drive down, closing a two-way valve, or closing

the L (lower) port and opening the U (upper) port of a three way valve. The valve

stem will drive up upon loss of signal.

Switch #2

Factory default - ON

Upon loss of power the Enerdrive® circuit will drive the valve stem down, closing a two-way valve, or closing

the L (lower) port and opening the U (upper) port of a three-way valve. When Switch #2 is in the OFF position, upon loss of power the

Enerdrive® circuit will drive the valve stem up, opening a two-way valve or opening the L (Lower) port and closing the U (upper) port of a

three-way valve.

Switch #3

Factory default - ON

The motor will accept a 4-20 mAdc control signal connected to terminals 1(-) and 3(+) on terminal block 1.

When Switch #3 is in the OFF position the motor will accept a 2-10 vdc signal.

Switch #4

Factory default - OFF

The motor will provide a 4-20 mAdc feedback output at terminals 1(-) and 5(+) on terminal block 1. When

Switch #4 is in the ON position the motor will provide a 2-10 vdc output.

Switch #5

(2-way) Factory default - ON This establishes a linear relationship between the control signal and valve stem lift. When Switch #5 is in the

OFF position a “non-linear” relationship is established between the control signal and valve stem lift. This is uniquely applicaple only on 2-way

valve linkages.

(3-way) Factory default - OFF

The 3-way linkage has a different signal to lift relationship and should not use the linearization feature.

For 3-way valves, switch #5 should always be

off.

Placing dipswitch #5 in its ON (Linearizing) position accomplishes

several objectives that may be helpful in specific control valve

installations. One result is that the entire input signal range is

applied to modulating the valve opening. Only at the very end

of the signal range does the AmurAct linkage drive into lockup.

Another result is that the inherent characteristic of the control

valve is preserved. “Linearizing” operation can provide linear flow

control when using a valve having linear trim.

Placing dipswitch #5 on its OFF (Non-Linear) position causes the

valve stem to rise very slowly in the beginning of its stroke, and

to rise increasingly rapidly as the valve opens. This mode uses the

first 25% of the control signal to move the linkage into and out

of lockup. “Non-Linear” operation may be useful when additional

control is needed at low flow rates, and additional response is

required for changes in higher flow rates.

Selection of the linearization mode (dipswitch #5) can be made

during operation, and dipswitch #5 should be left in the position

that produces the better system control result.

dipswitches

switch #1: Action &

Signal Loss
switch #2: Power Fail
switch #3: Signal
switch #4: Feedback
switch #5: Linearization

mA Signal Rotation

Linearized

Stem Lift

Non

Linearized

Stem Lift

0.023438

4

90

0.000000

0.00000

4.15

90

0.000000

0.00000

4.2

72

0.000000

0.00000

4.5

65.5

0.0234375

0.00000

5

59

0.046875

0.00000

5.5

54.75

0.070313

0.00000

6

50.5

0.093750

0.00100

6.5

46.25

0.117188

0.002000

7

42

0.140625

0.003000

7.5

39

0.164063

0.007000

8

36

0.187500

0.012000

8.5

33.5

0.210938

0.016000

9

31

0.234375

0.019000

9.5

29

0.257813

0.028000

10

27

0.281250

0.040000

10.5

25

0.304688

0.051000

11

23

0.328125

0.062000

11.5

21.5

0.351563

0.077000

12

20

0.375000

0.093000

12.5

18.5

0.398438

0.111000

13

17

0.421875

0.130000

13.5

15.75

0.445313

0.150000

14

14.5

0.468750

0.172000

14.5

13.25

0.492188

0.196000

15

12

0.515625

0.221000

15.5

10.75

0.539063

0.256000

16

9.5

0.562500

0.288000

16.5

8.5

0.585938

0.333000

17

7.5

0.609375

0.367000

17.5

6.5

0.632813

0.421000

18

5.5

0.656250

0.480000

18.5

4.25

0.679688

0.537000

19

3

0.703125

0.609000

19.5

1.5

0.726563

0.678000

20

0

0.750000

0.750000

4

4.15 4.2 4.5

5 5.5 6 6.5 7 7.5 8 8.5 9 9.5 10

10.5 1

1

11.5 12 12.5 13 13.5 14 14.5 15 15.5 16 16.5 17 17.5 18 18.5 19 19.5 20

0.00000

0.10000

0.20000

0.30000

0.40000

0.50000

0.60000

0.70000

0.80000

Linearized Stem Lift
Non Linearized Stem Lift

mA signal

s

te

m

L

if

t

FOR 2-wAY ONLY