Limiti operativi, Funzionamento a freddo 8, Funzionamento a caldo 8 – Airedale EcoChill 6kW - 46kW User Manual

Page 18: Dati di progetto, Operating limits, Cooling mode, Cooling mode for condensing unit versions "c, Heating mode, Maximum ratings

Advertising
background image

18

EcoChill Installation Manual 7481930_v1.6.0_08_2013

ECL-ECLH 020-202

EN

8.

OPERATING LIMITS

Note:

8 In SUMMER mode the unit can be started with

external air 46°C and inlet water 35°C.

In WINTER operation the unit can be started with

external air -15°C and inlet water 20°C.

Operation in these conditions is only permitted for

a short time and to bring the system to operating

temperature.

To reduce this operating time it is recommended

to install a three way valve to allow water to be

bypassed from the system, until the permitted

operating limits of the unit are reached.

8.1. COOLING MODE

8

8.3. HEATING MODE

8

The units in standard configuration are not suited for

installation in saline environments.

For the operating limits refer to the diagrams which are

valid for Δt= 5K.

8.2. COOLING MODE FOR CONDENSING UNIT VERSIONS "C"

Ex

ternal air t

emper

atur

e °C db

Ex

ternal air t

emper

atur

e °C db

Leaving water temperature EVAPORATOR °C

EVAPORATING temperature °C

-10

-15

-10

-5

0

5

10

15

20

25

30

35

40

45

50

-9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

46

46

-10

-15

-10

-5

0

5

10

15

20

25

30

35

40

45

50

-9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

46

46

25
20
15

30

35

40

45

50

55

60

-10

-5

0

5

10

15

20

25

30

35

40

45

50

42 °C

50 °C

50 °C

External air temperature °C db

CONDENSER lea

ving w

at

er

temper

atur

e

Standard operation

Operation with DCPX

accessory

Operation

with glycol

Operation with glycol

and DCPX accessory

Operation with DCPX

accessory

Thermostatic valve °

Y

Z

Operation with DCPX

accessory

WARNING

If operation outside of these limits

is required we first recommend

contacting our commercial techni-

cal services.

WARNING

If the unit is installed in particu-

larly windy locations the provision

of wind barriers may be necessary

to avoid malfunctions.

REFRIGERANT SIDE

High pressure

side

Low pressure side

Maximum permitted pressure

bar

42

25

Maximum permitted temperature

°C

120

52

Minimum permitted temperature COOLING ONLY VERSIONS

°C

-10

-16

Minimum permitted temperature HEAT PUMP VERSIONS

°C

-10

-10

8.4. MAXIMUM RATINGS