Operating limits, Dr10-95, Dry coolers – Airedale Dry coolers DR10 User Manual

Page 16: Precision air conditioning

Advertising
background image


DR10-95

DRY COOLERS

16

Precision Air Conditioning

Technical Manual :6877401 12 / 2011

16

Dry coolers

Technical Manual :6877401 V1.1.0 02_2013

CAPACITY DATA
Standard Dry Cooler Fan

Water Entering / Leaving

Ambient

Temperature °C

25°C

30°C

35°C

40°C

45°C

Output

(kW)

Output

(kW)

Output

(kW)

Output

(kW)

Output

(kW)

DR55

35°C/30°C

55

-

-

-

-

40°C/35°C

91.2

54.8

-

-

-

45°C/40°C

126.3

90.4

54.4

-

-

50°C/45°C

161.2

125.1

89.6

54

-

55°C/50°C

196

159.5

123.8

88.7

53.7

DR70

35°C/30°C

74.7

-

-

-

-

40°C/35°C

122.6

74.2

-

-

-

45°C/40°C

169.4

121.5

73.7

-

-

50°C/45°C

215.8

167.6

120.3

73.1

-

55°C/50°C

262.1

213.4

165.8

119.2

72.6

DR75

35°C/30°C

72.6

-

-

-

-

40°C/35°C

121.5

72.3

-

-

-

45°C/40°C

169.2

120.6

72

-

-

50°C/45°C

216.6

167.7

119.6

71.6

-

55°C/50°C

263.8

214.5

166.2

118.7

71.2

DR95

35°C/30°C

98.5

-

-

-

-

40°C/35°C

163.3

97.9

-

-

-

45°C/40°C

226.7

162

97.4

-

-

50°C/45°C

289.7

224.6

160.6

96.7

-

55°C/50°C

352.6

286.9

222.5

159.3

96.1

(1) Output kW refers to the dry cooler heat rejection

Operating Limits

Standard Variable Speed Head Pressure Control
Minimum Ambient Air DB °C

-20°C

Maximum Ambient Air DB °C

+48

Optional On/Off Head Pressure Control
Minimum Ambient Air DB °C

-0°C

Maximum Ambient Air DB °C

+48

(1)

For conditions outside those quoted, please contact Airedale.