Dr10-95, Dry coolers, Precision air conditioning – Airedale Dry coolers DR10 User Manual

Page 22: Mechanical data- condensers and dry coolers

Advertising
background image


DR10-95

DRY COOLERS

22

Precision Air Conditioning

Technical Manual :6877401 12 / 2011

22

Dry coolers

Technical Manual :6877401 V1.1.0 02_2013

Mechanical Data- Condensers and Dry Coolers

DR75

DR70

DR95

Total Heat of Rejection DR

(1)

kW

72

73.7

97.4

Dimensions - Horizontal

(2)

H x W x L

mm

1167 x 1000 x 3565

1167 x 1000 x 4641

1167 x 1000 x 4641

Dimensions - Vertical

(2)

H x W x L

mm

1155 x 1167 x 3565

1090 x 1167 x 4641

1155 x 1167 x 4641

Weight

Machine

kg

310

349

415

Construction

Material/Colour

Galvanised Sheet Steel, Epoxy Baked Powder Paint - Light Grey (RAL 7035)

Dry Cooler

Air Cooled - Copper Tube/Turbulated Aluminium Fins

Total Face Area

3.63

4.8

4.8

Nominal Airflow

m³/s

9.3

8.7

12.4

Discharge

-H Horizontal or -V Vertical (Please Specify at Order)

Fan & Motor

Axial

Quantity

3

4

4

Diameter

mm

710

630

710

Maximum Speed

rpm

930

895

930

Dry Cooler

Internal Water Volume

L

43.2

55.9

55.9

Water flowrate

l/s

3.4

3.5

4.6

Pressure Drop

kPa

53

62

94

OPTIONAL EXTRAS

Short Case Axial Fan

Designed to 75 Pa ESP

Dimensions

– Horizontal

H x W x L

mm

1140 x 1000 x 3565

1167 x 1000 x 4641

1167 x 1000 x 4641

Dimensions

– Vertical

H x W x L

mm

1140 x 1167 x 3565

1130 x 1167 x 4641

1140 x 1167 x 4641

Weight

Machine

kg

345

394

404

EC Fan

Dimensions

– Horizontal

H x W x L

mm

1167 x 1000 x 3565

1167 x 1000 x 4641

1167 x 1000 x 4641

Dimensions

– Vertical

H x W x L

mm

1170 x 1167 x 3565

1127 x 1167 x 4641

1170 x 1167 x 4641

Weight

Machine

kg

301

375

462


(1) Nominal data based on 35°C ambient and a 45/40°C Water entering/leaving.
(2) Overall dimensions for clearance; refer to

Dimensional & Installation Data

, for detail.

Advertising